Advanced Analysis of HVDC Electrodes Interference on Neighboring PipelinesReportar como inadecuado




Advanced Analysis of HVDC Electrodes Interference on Neighboring Pipelines - Descarga este documento en PDF. Documentación en PDF para descargar gratis. Disponible también para leer online.

This paper focuses on advanced analysis techniquesand design considerations of DC interference generated by HVDC electrodesduring normal bipolar and temporary monopolar operations on neighboringmetallic utilities, with a special emphasis on buried gas and oil pipelines. Thisstudy examines the level of pipeline corrosion, the safety status in thevicinity of exposed appurtenances and the impact of DC interference on the integrityof insulating flanges and impressed current cathodic protection ICCP systems.Computation results obtained for different soil models show that differentsoils can lead to completely different DC interference effects. The results andconclusions presented here can be used as a reference to analyze the severityof DC interference on pipelines due to proximate HVDC electrodes.

KEYWORDS

HVDC Electrode, DC Interference, Pipe-to-Soil Potential, Polarization Potential, Insulating Joint Flanges, Rectifier, Touch Voltage, Corrosion, Safety, Impressed Current Cathodic Protection

Cite this paper

Gong, Y. , Xue, C. , Yuan, Z. , Li, Y. and Dawalibi, F. 2015 Advanced Analysis of HVDC Electrodes Interference on Neighboring Pipelines. Journal of Power and Energy Engineering, 3, 332-341. doi: 10.4236-jpee.2015.34045.





Autor: Yu Gong1, Chunlin Xue2, Zhilei Yuan2, Yexu Li3, Farid Paul Dawalibi3

Fuente: http://www.scirp.org/