Optimal Capacity Allocation for a Failure Resilient Electrical InfrastructureReportar como inadecuado




Optimal Capacity Allocation for a Failure Resilient Electrical Infrastructure - Descarga este documento en PDF. Documentación en PDF para descargar gratis. Disponible también para leer online.

1 Chaire Sciences des Systèmes et Défis Energétiques EDF-ECP-Supélec LGI - Laboratoire Génie Industriel - EA 2606, SSEC - Chaire Sciences des Systèmes et Défis Energétiques EDF-ECP-Supélec

Abstract : In this study, we tackle the problem of searching for the most favorable pattern of link capacities that makes a power transmission network resilient to cascading failures with limited investment costs. This problem is formulated within a combinatorial multi-objective optimization framework and tackled by evolutionary algorithms. A power flow model namely, the ORNL-Pserc-Alaska OPA model is embraced to simulate cascading failures in a network and to quantify its resilience. The framework of capacity allocation optimization is originally applied to the 400kV French power transmission network for the purpose of exemplification. The results show that cascade resilient networks tend to have a non-linear capacity-load relation: in particular, heavily loaded components have smaller unoccupied portion of capacity, whereas lightly loaded links present larger unoccupied portion of capacity which is in contrast with the linear capacity-load relation hypothesized in previous works.

Keywords : power transmission network evolutionary algorithm capacity optimization cascading failures power flow model





Autor: Yi-Ping Fang - Nicola Pedroni - Enrico Zio -

Fuente: https://hal.archives-ouvertes.fr/



DESCARGAR PDF




Documentos relacionados